Walls and Roof

Subslab assembly

Sub slab: dirt crawl spaces with two inches of Styrofoam under a plastic liner conditioned mechanical space basement with Anvantech flooring over two inches of Styrofoam and Patton polyethylene sheets

Foundation wall assembly

Existing, R-40 (rater indicates R-15) 8“ of closed cell foam over plastic wall liner with offset steel studs and covered with paperless drywall
Addition, R-20 (rater indicates R-23) 8“ of sprayed closed cell foam over continuous plastic wall

Above grade wall assembly

Existing, R-56 (rater indicates-47) offset wall studs with 8“ sprayed closed cell foam
Addition, R-52 off set wall studs with 8” of closed cell foam

8” double offset stud wall new addition and all existing exterior walls to offset thermal bridging and increase depth of foam insulation
American Clay over existing plaster or new wall board throughout

Cathedral ceiling assembly

Existing, R-72 +/- three by four rafters joined with new 8” rafters, the resulting cavity filled with closed cell foam, and then four inches of Styrofoam over plywood and recycled rubber underlayment
Addition, R-86 (rater indicates R-120 for both) new 10” rafters, the resulting cavity filled with closed cell foam, and then four inches of Styrofoam over plywood and recycled rubber underlayment

Roof Assembly

Sprayed foam underside of new or existing deck and 4” of Styrofoam over Strong Seal Rubber underlayment. Finished with furring strips and standing seam metal roofing

Windows and Doors

Window Assembly:

Marvin Integrity windows on the north, east and west sides of the building with Comfortex, Comfor-Track Plus cellular shades; on the south side Magnetic One Lite storm windows by Allied Windows interior of the rebuilt antique original windows and exterior wooden storm sashes. The Marvin casement windows have a U value of .29 and SHGC of.30.

Door Assembly:

The new doors are made by Thermo-Tru and are Energy star rated with a U value of 0.26 and a SHGC of 0.17

Average window U-factor 0.29
Solar Heat Gain Coefficient 0.30
Door U-Factor 0.26

Mechanical Systems

Space cooling - Manufacturer & Model Climate Master Tranquility TT038 Ground Source Heat Pump (Energy Star Rated) (6894 Heating degree days per designer)
Space heating - Manufacturer & Model Climate Master Tranquility TT038 Ground Source Heat Pump (Energy Star Rated) (6894 Heating degree days per designer)
Domestic hot water - Manufacturer & Model Solar Hot Water - Velux Model CLI-U12SKOW/L218EL, SRCC Rated SEF 3.6
Domestic hot water - capacity 80 gal
Ventilation - Manufacturer & Model LifeBreath (200Max) Heat Recovery Ventilator (Energy Star Rated), Air King ESSEV 30 kitchen range hood(Energy Star Rated), Ultra-air Whole House Dehumidifier 100V(Energy Star Rated), (6) ceiling fans(Energy Star Rated)
Lighting Manufacturer and Model 19 Energy Star rated either CFL or LED light fixtures with the remaining 14 CFL equipped recessed fixtures
Lighting Efficiency

Envelope

Air Changes per hour, ACH50 2.54 ACH50
Air Changes per hour, CFM50 1 110.00