The envelope consists of a number of assemblies. Window to wall ratio is 22%.
Wall assemblies are a combination of stud and mass wall. The approach to stud assemblies to fill the stud cavity with mineral wool insulation and put 3 inches of mineral wool insulation outboard of the vapor barrier. The approach at mass walls is similar, except that the stud cavity, which is shallower, is filled with foam-in-place insulation.
The air-vapor barrier is continuous, with carefully designed transitions and tie-ins at openings.
Subslab assembly |
Slab on grade - 6" th. |
---|---|
Subslab R-value | 10.0 |
Foundation wall assembly |
Foundation wall is essentially a frost wall. There is no basement. It is not insulated. |
Above grade wall assembly |
Cladding (brick, wood, metal panel) |
Above grade wall R-value | 20.6 |
Roof Assembly |
Modified bituminous membrane roofing |
Roof R-value | 22.2 |
Windows and Doors
Window Assembly:
Curtainwall
Aluminum
Kawneer
1600UT
Storefront
Aluminum
Kawneer
451UT
Door Assembly:
Aluminum
Kawneer
500
Average window U-factor | 0.29 |
---|---|
Solar Heat Gain Coefficient | 0.22 |
Visible Light Transmittance | 0.41 |
Door U-Factor | 0.51 |
Door Area | 336 sq ft |
Mechanical Systems
Space cooling - Manufacturer & Model | Ground-source: Multistack MS030, MS050, MS070, Air-source: Airstack ARP060XN14H2RS0AAAEN-410A, Fan Coil Units: Airtherm Unitaire CPFR 121 |
---|---|
Space cooling - capacity | 1,000 kW |
Space heating - Manufacturer & Model | Ground-source: Multistack MS030, MS050, MS070, Air-source: Airstack ARP060XN14H2RS0AAAEN-410A, Fan Coil Units: Airtherm Unitaire CPFR 121 |
Space heating - capacity | 450 kW |
Domestic hot water - Manufacturer & Model | Kingspan Solar collectors HP-450 |
Domestic hot water - capacity | 500 gal |
Domestic hot water - efficiency | 65 kW |
Ventilation - Manufacturer & Model | Haakon (Custom manufactured) |
Lighting Manufacturer and Model | Gotham (various models), Portfolio (various models), Lithonia (various models), Pinnacle (various models) |
Lighting Efficiency | 0.58 W/sf |
Mechanical Equipment Installation Details and Comments |
Complete construction administration and commissioning process. Also studied BAS dashboard output related to systems to ensure proper operation. |